查了一下士林電機的規格s-p11◎額定容量CNS AC3級 3相 220~240V→kw/HP/A:3/4/12 380~440V→kw/HP/A:4/5.5/9最大承受到12A而已(220V環境下)你家的如果有真的也用到35A要買到更高規格的才行
5007382 wrote:你控制是DC應該要買...(恕刪) MC對於A/DC等不同的負載電流,其啟斷能力是不同的,不可只看其額定電流(大多數之額定電流,以AC-1定義,但這是最寬鬆的負載),還必須確認屬於何種用電負載,許多電機工作者都不懂,也不會去翻規範.請參閱 IEC-60947-4-1 2000 Table-1的定義Kind of current Utilization categories Typical applicationsAC-l Non-inductive or slightly inductive loads, resistance furnaces.AC-2 Slip-ring motors: starting, switching off.AC-3 Squirrel-cage motors : starting, switching off motors duringrunning.AC-4 Squirrel-cage motors : starting, plugging. Inching.AC-5a Switching of electric discharge Ismp controls.AC-5b Switching of incandescant lamps.AC-6a Switching of transformers.AC-6b Switching of capacitor banks.AC-7a Slightly inductive loads in household appliances and similar applications.AC-7b Motor-loads for household applications.AC-8a Hermetic refrigerant compressor motor control with manual resetting of overload releases.AC-8b Hermetic refrigerant compressor motor control with automatic resetting of overload releases.DC-1 Non-inductive or slightly inductive loads. resistance furnaces.DC-3 Shunt-motors: starting. plugging. Inching Dynamic breaking of d.c. motors.DC-5 Series-motors : starting. plugging. Inching Dynamic breaking of d.c. motors.DC-6 Switching of Incandescent lamps.
stish wrote:規格寫的是交流環境下...(恕刪) 別鬧了,你並聯下去,送電就知道啥是跳電了@@"另外NO改NC,可以去買輔助接點來加裝即可只是~~~輔助接點會比電磁接觸器本身容易故障用久了有時會卡住造成設備故障